⚡ Alpha Build (v1.1) — Active Development — Verify Critical Calculations ⚡

Wire Ampacity & Derating

NEC Table 310.16 with 310.15 Heat & Bundling Adjustments.

1. Conductor Properties

NEC 110.14(C)(1)(a): Circuits ≤100A (#14–#1 AWG) default to 60°C unless equipment/breakers at both ends are marked for 75°C.

2. Derating Conditions (NEC 310.15)

LEGAL DISCLAIMER:Estimates based on NEC Table 310.16, 310.15(B)(1), and 310.15(C)(1). Always verify with a licensed professional.

Allowable Ampacity

25.0A
Allowable Conductor Ampacity
Max General OCPD (240.4(D)): 20A Breaker
Base (90°C Col)30 A
Multipliers (Temp × Bundle)1.15 × 1
Derated Calculation34.5 A
Terminal Cap (75°C)25 A
NEC 240.4(D) Small Conductor Rule:Max general overcurrent breaker/fuse for 12 AWG (Cu) is capped at 20 Amps.